Industrial-grade Rectifier and Battery Charger
Spectra II Rectifier Battery Charger

Product Highlights

  • Robust and reliable layout for industrial applications
  • Standard configurations for cost effective, short lead time solutions
  • Microprocessor control
  • Full set of battery charging methods with battery voltage/temperature compensation
  • Extensive range of options and customized solutions
  • Easy accessibility and maintenance
  • Description

    Alpha’s Spectra II Rectifier Battery Charger is a robust, industrial-grade rectifier, designed to supply critical DC loads and charge all battery types. Based on standardized IGBT power conversion systems and available in various rated enclosures, this power system provides superior reliability, efficiency and cost effectiveness for mission-critical applications such as Oil & Gas plants, Power Stations and Substations, Manufacturing plants and Transportation.


    • AC Input
      Standard Voltages Single Phase 120, 208, 240
      Three Phase 208, 240, 380, 480, 600
      Frequency 50/60 Hz ± 5 Hz   
      Efficiency >90%   
      Power Factors >90% (Single Phase)
      >95% (Three Phase – 12 pulse) OUTPUT   
           
      DC Output
      Standard Voltages  Nominal Battery Voltages: 24, 48, 120, 240 VDC    
      Current Ratings  10, 20, 30, 40, 50, 100, 150, 200, 320, 500 AMPS    
      Charging Charasteristics  IU (DIN 41773), U1U2I, I1I2U    
      Recommended Operating Voltages (V/Cell, Adjustable)   NiCad    VLA  VRLA
       Float  1.40 - 1.50  2.20 - 2.30  2.27
       Equalize  1.50 - 1.65  2.40 - 2.45  -
       Refresh  1.70  2.70  -
       Output Regulation  Static Voltage Regulation: <1% - Voltage Ripple: <1%
       Overload Capacity <120% for 30 minutes
      <150% for 3 minutes
      >150% for 3
       
      Protection
      Battery Polarity Reversal If the battery is connected with reverse polarity, the rectifier remains in stand-by mode and gives error/warning message.
      Electronic Overload Protection Complete protection in case of output short circuit, overload, over-temperature
      Anti-Arcing When the battery is connected, no arcing is generated at the connectors
      Power-On Self-Test Every time the unit is powered, an automatic self-test of the power electronics and the control boards is executed in less than 10 seconds. In case of fault, the unit remains in safe stand-by mode and gives fault messages.
    Mechanical
    • Dimensions
      W x H x D (in/mm):
      CABINET A: 19.7 x 35.4 x 17.3/ 500 x 900 x 440
      CABINET B: 21.7 x 51.2 21.7/ 550 x 1300 x 550
      CABINET C: 31.5 x 63 x 19.7/ 800 x 1600 x 500
      CABINET D: 31.5 x 78.7 x 23.6/ 800 x 2000 x 600
       
      Color: RAL 7035, Light Gray
    Environmental
    • Cooling:  Rating dependent
      Audible Noise: <65 dBA at 1 meter
      Environmental Protection: IP21 (Standard), IP31 (Optional), IP54 (Optional)
      NEMA 1, NEMA 3R, NEMA 12
      Ambient Temperature: OPERATION: -10/ +50 C
      STORAGE: -20/ +70 C
      Altitude: <2000m
      Derating according to EN62040-3
    Options
      • Output Blocking diode for parallel operation
      • Battery breaker
      • Battery on racks or inside cabinets
      • Earth fault monitoring and alarm
      • Fan monitoring and alarm
      • Remote relay alarms
      • Redundant supply for control
      • Enclosure type IP54, IP31
      • MODBUS RTU over RS485
      • MODBUS TCP over Ethernet
      • DNP3 over Ethernet
      • DNP3 over RS485
    User Interface
    • User Interface: Alphanumeric LCD Display, 5x LEDs, keyboard and Audible
      Connectivity: RS-232/Hyper Terminal (Standard)
    Standards
    • Quality: ISO 9001:2008
      Marking: CE, UL 1012, UL 60950
      EMC: IEC EN 61000-6-2, IEC EN 61000-6-4
      Safety: IEC EN 50178, IEC EN 62040-1, UL 1012, UL 60950